Guide · 5 min read

How to connect 48 V lithium batteries in parallel

Same model, same voltage, equal cables, linked communication ports and the right inverter settings. Here is the order to do it in.

The short answer: batteries in parallel add their kWh and their current while staying at 51.2 V. Use the same model, bring them to the same voltage before connecting, wire them so every unit sees the same cable resistance, link their communication ports, and set the inverter for the whole bank. Most of our 51.2 V models allow up to 15 units in parallel.

Parallel, not series

A 48 V inverter needs 51.2 V, so 51.2 V batteries are connected in parallel: positive to positive, negative to negative. Do not put 51.2 V units in series to reach a higher voltage. High-voltage inverters use high-voltage battery modules built for series stacking, such as our KNY-HV102100.

What a bank gives you

Units in parallelWith 10 kWh unitsWith 16 kWh unitsRecommended currentInverter power at that current
110.24 kWh16.08 kWh100 Aabout 4.9 kW
220.48 kWh32.16 kWh200 Aabout 9.7 kW
330.72 kWh48.24 kWh300 Aabout 14.6 kW
440.96 kWh64.32 kWh400 Aabout 19.5 kW

Recommended current is 100 A per unit for our 10–20 kWh models; check the inverter’s own limits too.

Before you connect

  • Same model and capacity. Mixing sizes or makes in one bank makes the units share current unevenly.
  • Same voltage. Charge every unit fully, or at least to the same state of charge, before connecting them. Joining a full battery to an empty one makes a large current flow between them.
  • Check the limit. Most of our 51.2 V models allow up to 15 units in parallel. Our Bluetooth 25.6 V 100 Ah and 200 Ah packs allow 2.
  • Switch off. Turn off the inverter, the battery breakers and the PV input before working on the DC side.

Wiring the bank

  • Use a busbar, or equal cables. Run a cable of the same length and size from each battery to a positive and a negative busbar, then one pair from the busbars to the inverter. Equal resistance means equal sharing.
  • If you link batteries in a chain, take the inverter’s positive from the first battery and its negative from the last, so the current path is the same length for every unit.
  • Size the main cables for the total current, for example about 200 A for a 10 kW inverter, and fit a DC breaker or fuse rated for it.
  • Tighten the terminals to the torque in the manual. A loose lug heats up under load.

Communication and addresses

  • Link the batteries’ communication ports with the supplied cables, so the units report to each other.
  • Give each battery its own address as the manual describes, usually with small DIP switches on the panel. The first unit is normally the one that talks to the inverter.
  • Connect that unit to the inverter by CAN or RS485 and select the matching battery protocol on the inverter. The inverter then reads the state of charge and the charge limits of the whole bank.

Inverter settings for the bank

  • Maximum charge current: the number of units × the recommended current per unit, up to the inverter’s own limit.
  • Charge voltage: 58 V recommended, never above 58.4 V on our 51.2 V models. Discharge cut-off: 46 V recommended.

Adding a battery later

Charge the existing bank and the new unit to full, connect the new unit with cables of the same length as the others, set its address and restart the system. A new unit next to older ones is normal; the battery management system keeps them working together.

Sizing first? See what size battery a 10 KVA inverter needs and how many kWh a home needs.

More guides

6 min readHow many kWh of battery does a home need?

A four-step method with worked examples for backup, evening use and air conditioning at night.

Read the guide →
4 min read48 V or high-voltage battery: which one fits?

Inverter match, current and cables, expansion and installation, side by side.

Read the guide →
4 min readHow long will a 10 kWh battery power a home?

A runtime table from 100 W to 5 kW, typical appliance loads and an example evening.

Read the guide →
3 min readHow many Ah is a 16 kWh battery?

Convert kWh to Ah and back at 12, 24 and 48 V, with a table for every common battery size.

Read the guide →
4 min readWhat size lithium battery for a 5 KVA inverter?

Battery current at full load, backup hours for 10–20 kWh, and when to add a second unit.

Read the guide →
5 min readLithium or tubular battery for an inverter?

Usable energy, cycle life, charging, maintenance and space, side by side.

Read the guide →
4 min readHow many solar panels to charge a 10 kWh battery?

The formula, a table for 5–20 kWh at 4–6 sun hours, and the daytime load.

Read the guide →
4 min readWhat size lithium battery for a 3.5 KVA inverter?

24 V or 48 V, the current at full load, and backup hours for 5–15 kWh.

Read the guide →
4 min readWhat size lithium battery for a 10 KVA inverter?

Battery current at 6–11 kW, backup hours for 2 and 3 units, and the settings.

Read the guide →
5 min readShipping lithium batteries from China: documents and sea freight

UN 3480 by sea, UN38.3 and MSDS, choosing a forwarder, Kenya and Nigeria certificates.

Read the guide →

Need help sizing a system?

Send us the loads, the inverter and the market. We recommend a battery and reply with the datasheet and price.

WhatsApp