The short answer: batteries in parallel add their kWh and their current while staying at 51.2 V. Use the same model, bring them to the same voltage before connecting, wire them so every unit sees the same cable resistance, link their communication ports, and set the inverter for the whole bank. Most of our 51.2 V models allow up to 15 units in parallel.
Parallel, not series
A 48 V inverter needs 51.2 V, so 51.2 V batteries are connected in parallel: positive to positive, negative to negative. Do not put 51.2 V units in series to reach a higher voltage. High-voltage inverters use high-voltage battery modules built for series stacking, such as our KNY-HV102100.
What a bank gives you
| Units in parallel | With 10 kWh units | With 16 kWh units | Recommended current | Inverter power at that current |
|---|---|---|---|---|
| 1 | 10.24 kWh | 16.08 kWh | 100 A | about 4.9 kW |
| 2 | 20.48 kWh | 32.16 kWh | 200 A | about 9.7 kW |
| 3 | 30.72 kWh | 48.24 kWh | 300 A | about 14.6 kW |
| 4 | 40.96 kWh | 64.32 kWh | 400 A | about 19.5 kW |
Recommended current is 100 A per unit for our 10–20 kWh models; check the inverter’s own limits too.
Before you connect
- Same model and capacity. Mixing sizes or makes in one bank makes the units share current unevenly.
- Same voltage. Charge every unit fully, or at least to the same state of charge, before connecting them. Joining a full battery to an empty one makes a large current flow between them.
- Check the limit. Most of our 51.2 V models allow up to 15 units in parallel. Our Bluetooth 25.6 V 100 Ah and 200 Ah packs allow 2.
- Switch off. Turn off the inverter, the battery breakers and the PV input before working on the DC side.
Wiring the bank
- Use a busbar, or equal cables. Run a cable of the same length and size from each battery to a positive and a negative busbar, then one pair from the busbars to the inverter. Equal resistance means equal sharing.
- If you link batteries in a chain, take the inverter’s positive from the first battery and its negative from the last, so the current path is the same length for every unit.
- Size the main cables for the total current, for example about 200 A for a 10 kW inverter, and fit a DC breaker or fuse rated for it.
- Tighten the terminals to the torque in the manual. A loose lug heats up under load.
Communication and addresses
- Link the batteries’ communication ports with the supplied cables, so the units report to each other.
- Give each battery its own address as the manual describes, usually with small DIP switches on the panel. The first unit is normally the one that talks to the inverter.
- Connect that unit to the inverter by CAN or RS485 and select the matching battery protocol on the inverter. The inverter then reads the state of charge and the charge limits of the whole bank.
Inverter settings for the bank
- Maximum charge current: the number of units × the recommended current per unit, up to the inverter’s own limit.
- Charge voltage: 58 V recommended, never above 58.4 V on our 51.2 V models. Discharge cut-off: 46 V recommended.
Adding a battery later
Charge the existing bank and the new unit to full, connect the new unit with cables of the same length as the others, set its address and restart the system. A new unit next to older ones is normal; the battery management system keeps them working together.
Sizing first? See what size battery a 10 KVA inverter needs and how many kWh a home needs.