The short answer: a 10 KVA inverter on 48 V needs at least two 51.2 V LiFePO4 batteries in parallel. At full power it draws about 200 A from the battery, while each of our 10–20 kWh units is rated 100 A recommended and 200 A maximum. Two 10 kWh units (20.48 kWh) suit evening use and power cuts; two or three 16 kWh units suit air conditioning, pumps or off-grid homes.
Step 1: Size on kW, not KVA
Some 10 KVA inverters deliver 8 kW; many newer hybrid and off-grid models deliver 10 to 11 kW. Our UD12548AM is rated 10,000 W, the XD16048 10,600 W and the 11 kW models in the GD Pro and QD series 11,000 W. The battery current follows the watts.
Step 2: Count the current
| Inverter output | Battery current | Per unit, 2 in parallel | Per unit, 3 in parallel |
|---|---|---|---|
| 6,000 W | about 123 A | about 62 A | about 41 A |
| 8,000 W | about 164 A | about 82 A | about 55 A |
| 10,000 W | about 206 A | about 103 A | about 69 A |
| 11,000 W | about 226 A | about 113 A | about 75 A |
Battery current = inverter output ÷ 51.2 V ÷ about 95% inverter efficiency.
One 10–20 kWh unit can supply 200 A at its maximum rating, but running it there for hours is not what it is designed for. With two units in parallel each carries about 100 A at 10 kW, which is its recommended current. With three, each carries about 70 A, which leaves room for inverter surges and long hot afternoons.
Step 3: Decide the hours
| Average load | 2 × 10 kWh 20.48 kWh | 2 × 16 kWh 32.16 kWh | 2 × 20 kWh 40.96 kWh | 3 × 16 kWh 48.24 kWh |
|---|---|---|---|---|
| 1,000 W | 14.7 h | 23.2 h | 29.5 h | 34.7 h |
| 2,000 W | 7.4 h | 11.6 h | 14.7 h | 17.4 h |
| 3,000 W | 4.9 h | 7.7 h | 9.8 h | 11.6 h |
| 5,000 W | 2.9 h | 4.6 h | 5.9 h | 6.9 h |
Using 80% of the rated energy and 90% inverter efficiency. Batteries in parallel add their kWh.
Our suggestion for a 10 KVA inverter
| How the inverter is used | Battery bank |
|---|---|
| Evenings and power cuts, about 1–2 kW average | Two 10 kWh units, 20.48 kWh |
| Air conditioning at night, pumps, a small shop | Two 16 kWh or two 20 kWh units |
| Off-grid, or near full power for hours | Three 16 kWh units, 48.24 kWh |
Settings for two or more batteries
- Charge current: up to the number of units × 100 A, but never above the inverter’s own maximum charge current.
- Charge voltage: 58 V recommended, never above 58.4 V on our 51.2 V models.
- Communication: link the batteries to each other and connect one of them to the inverter by CAN or RS485, so the inverter reads the state of charge of the whole bank.
Wiring, communication cables and adding a unit later are covered in how to connect batteries in parallel. If the inverter is a high-voltage hybrid model instead of 48 V, see 48 V vs high-voltage batteries.